In conventional data centre power architectures, uninterruptible power supplies are typically installed indoors on the low-voltage side. Vertiv is now moving the UPS outdoors to the 34.5kV medium-voltage grid connection point.

On 12 November, Vertiv launched the PowerNexus MV UPS. Under the new architecture, the UPS is no longer positioned on the indoor low-voltage side but moved upstream to the outdoor 34.5kV point of interconnection. Medium-voltage backup power, fault ride-through, AI load smoothing, reactive power and harmonic compensation, and long-duration energy storage control are brought together within a single system architecture.

The change involves more than equipment location. Traditionally, a UPS has primarily been used to keep critical loads running after a grid outage. PowerNexus MV UPS is also designed to manage fluctuations in AI workloads, support more grid-friendly operation and provide extended backup duration. The role of the UPS is beginning to extend beyond an internal backup system to become a power interface between the data centre and the grid.

1111111111111111111111111111111111111.png

Why Move the UPS to the Medium-Voltage Side?

A conventional data centre typically steps medium-voltage grid power down to low voltage before delivering it through low-voltage UPS and distribution systems to IT loads, with batteries providing backup energy for the UPS.

This architecture has been used for many years, but its limitations become more pronounced as the power requirements of AI data centres continue to increase. More conversion stages mean greater losses, more equipment interfaces and higher system complexity. UPS and associated distribution equipment also occupy valuable indoor space that could otherwise be used for servers and liquid-cooling infrastructure.

PowerNexus MV UPS moves power protection upstream to the 34.5kV medium-voltage side. According to Vertiv's product information, the system is rated at 3.0 MVA and uses a modular 40-foot outdoor enclosure integrating reactors, a coupling transformer, dual power conversion systems and controls. Peak efficiency in AC-to-AC operation can reach 98.5%.

22222222222222222222222222222222222.png

The transformer, reactors, power converters and control system are pre-assembled and pre-tested at the factory, reducing interface coordination after the equipment arrives on site. Moving critical power infrastructure outdoors can also leave more indoor space available for computing equipment.

However, the product is primarily intended for new AI data centres and expansion projects. It is not designed as a direct retrofit for existing low-voltage UPS systems.

Energy Storage No Longer Waits for an Outage

PowerNexus MV UPS can be connected to separately deployed long-duration battery containers, providing between one and four hours of backup.

During normal grid operation, the PCS handles bidirectional power conversion, battery charging, reactive power control and harmonic compensation, while the overall system smooths fluctuations in AI workloads. If the grid fails, the PCS switches to battery power to continue supporting critical loads.

Within this architecture, energy storage is clearly no longer a battery that remains idle until an outage occurs. It begins to address three different requirements:

  • Reducing the transmission of rapid AI load fluctuations to the upstream grid
  • Maintaining critical loads during grid voltage sags or overvoltage events
  • Reducing dependence on diesel generators during extended outages through one to four hours of battery backup

Vertiv has combined UPS functionality and long-duration storage within a unified solution, reducing the interface coordination and on-site commissioning associated with procuring different systems separately.

However, "integrated" in this context primarily refers to electrical architecture and control systems. The batteries remain housed in separate containers and are not connected directly to the 34.5 kV bus.

AI Load Fluctuations Need to Be Contained Before They Reach the Grid

AI training and inference workloads can produce rapid changes in power demand. If those fluctuations pass directly upstream, the grid sees a large electrical load that is constantly changing. This can affect power quality and make it more difficult for network operators to accommodate large, highly variable loads.

By positioning PowerNexus MV UPS at the point of interconnection, the system can smooth AI load fluctuations before they reach the grid. It also provides fault ride-through capability, allowing critical loads to remain operational during short-duration grid disturbances.

Vertiv has completed a proof-of-concept demonstration with QTS, SoftBank and Rosendin in Bologna, Italy. According to the company, the system operated stably across a load range of 0% to 100%, maintained IEC 62040-3 Class 1 voltage quality during rapid load changes, rode through a 100% voltage sag lasting 150 milliseconds, and withstood a 25% overvoltage event lasting five seconds.

These tests provide an initial demonstration of the system's ability to manage load changes and voltage disturbances. However, they were conducted as a proof of concept in a research and development facility and do not represent long-term operation in a commercial project.

PowerNexus MV UPS has now been launched, but it has not yet entered volume delivery.

Vertiv said it is engaging with customers globally and expects shipments to begin in mid-2027. The company's medium-voltage laboratory in Bologna is also scheduled to begin operation in 2027, supporting research, full-voltage testing and customer validation of architectures including medium-voltage UPS, medium-voltage-to-800 V DC conversion and battery energy storage.

Medium-voltage-to-800 V DC conversion is one of the future testing areas planned for the laboratory. It is not a disclosed output capability of PowerNexus MV UPS.

Vertiv has not yet announced product pricing, initial commercial orders, battery suppliers or specific project deployments.